Ex i temperature measuring transducer: Converts signals from resistance thermometers installed in Ex areas and transmits a 0/4-20 mA signal to a load in the safe area. Freely programmable, 3-way isolation.
Your advantages:
- Power supply possible via DIN rail connector;
- Input for resistance thermometers and resistance-type sensors, [Ex ia] IIC;
- Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter;
- Installation in zone 2, protection type "n" (EN 60079-15) permitted;
- 0 ... 20 mA or 4 ... 20 mA output;
- Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range;
- 3-way electrical isolation;
- Status indicator for supply voltage, cable, sensor, and module errors.
Dimensions
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Input data
Sensor types (RTD) that can be used
Sensors (2-, 3-, 4-wire)
Temperature measuring range
-200 °C ... 850 °C (Range depending on the sensor type)
Input signal range
0 Ω ... 2000 Ω
Cable resistance
≤ 50 Ω per cable
Sensor input current
200 μA ... 1 mA
Measuring range span
min. 50 K
Output data
Signal output
Current output
Configurable/programmable
Yes
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output
≤ 500 Ω
Output ripple (current)
< 50 µAPP
Behavior in the event of a sensor error
As per NE 43 or can be freely defined
Configurable/programmable
no
Power supply
Supply voltage range
19.2 V DC ... 30 V DC
Power dissipation
< 1 W
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
7 mm
Screw thread
M3
Connection method
Screw connection
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
General
No. of channels
1
Temperature coefficient, typical
0.01 %/K
Step response (0–99%)
typ. 700 ms
≤ 1100 ms
Alignment zero
± 5 %
Alignment span
± 5 %
Status display
Green LED (supply voltage, PWR)
Red LED, flashing 2.4 Hz (cable error, sensor error on input or output, ERR)
Red LED, flashing 1.2 Hz (service operation, ERR)
Red LED, permanently on (module error, ERR)
Flammability rating according to UL 94
V0
Degree of pollution
2
Overvoltage category
II
Interference emission
EN 61000-6-4
Housing material
PA 6.6-FR
Color
green
Designation
Input/output/power supply
Electrical isolation
300 Vrms (Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation
Input/output
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Designation
Input/power supply
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Conformance
CE-compliant, additionally EN 61326
ATEX
II (1) G [Ex ia Ga] IIC/IIB
II (1) D [Ex ia Da] IIIC
II 3(1) G Ex nA ic [ia Ga] IIC T4 Gc X
IECEx
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA ic [ia Ga] IIC T4 Gc
UL, USA/Canada
Class I Div 2; IS for Class I, II, III Div 1
Safety data
Max. output voltage Uo
6 V
Max. output current Io
6.3 mA
Max. output power Po
9.4 mW
Group
IIC
Max. external inductivity Lo
100 mH
Max. external capacity Co
1.4 µF
Group
IIC
Max. external inductivity Lo
10 mH
Max. external capacity Co
1.9 µF
Group
IIC
Max. external inductivity Lo
1 mH
Max. external capacity Co
2.7 µF
Group
IIB
Max. external inductivity Lo
100 mH
Max. external capacity Co
6.9 µF
Group
IIB
Max. external inductivity Lo
10 mH
Max. external capacity Co
9.4 µF
Group
IIB
Max. external inductivity Lo
1 mH
Max. external capacity Co
15 µF
Safety-related maximum voltage Um
253 V AC (125 V DC)
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
4 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
4 %
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
4 %
Standards and Regulations
Noise emission
EN 61000-6-4
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Flammability rating according to UL 94
V0
Conformance
CE-compliant, additionally EN 61326
ATEX
II (1) G [Ex ia Ga] IIC/IIB
II (1) D [Ex ia Da] IIIC
II 3(1) G Ex nA ic [ia Ga] IIC T4 Gc X
IECEx
[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA ic [ia Ga] IIC T4 Gc
UL, USA/Canada
Class I Div 2; IS for Class I, II, III Div 1
Group
IIC
IIC
IIC
IIB
IIB
IIB
New, in opened box.
Typical delivery time:
Economy shipping (Russian Post)
Standard Shipping (EMS Express Post)
Europe
14-30 days, in rare cases up to 60 days
7-20 days, in
very rare cases up to 60 days
United States
20-40 days, in rare cases up to 70 days
14-30 days, in rare cases up to 60 days
Canada
14-30 days, in rare cases up to 60 days
7-30 days, in rare cases up to 60 days
Asia, India, Africa
14-40 days, in rare cases up to 60 days
7-20 days, in
very rare cases up to 60 days
Australia and Oceania
14-40 days, in rare cases up to 60 days
10-25 days, in rare cases up to 60 days
South and Central America
20-40 days, in rare cases up to 70 days
14-30 days, in rare cases up to 60 days
Other countries
20-60 days, in rare cases up to 80 days
10-30 days, in rare cases up to 70 days